Automatic Standby Generator: Diesel, Liquid, Three Phase, 120/240V AC, CARB Compliant
Automatic Standby Generator: Diesel, Liquid, Three Phase, 120/240V AC, CARB Compliant

Product Image

Automatic Standby Generator: Diesel, Liquid, Three Phase, 120/240V AC, CARB Compliant

Item 32PL17 Mfr. Model # RD05033JDAE
In Stock
$30,272.00 /each
Earn 30272 points with this purchase
Request quantity discount pricing
You're Viewing
Automatic Standby Generator: Diesel, Liquid, Three Phase, 120/240V AC, CARB Compliant
GENERAC Automatic Standby Generator: Diesel, Liquid,...
Item 32PL17
$30,272.00
Customers Also Viewed

No related products found.

Product Details

Catalog Page 947
Brand GENERAC
Engine Block Heater Optional
CARB Compliant Yes
California Prop 65 Cancer N
Battery Group Number Group 27F
Engine Oil Capacity 11.6 qt
Manufacturer Part Number RD05033JDAE
Rated Current @ 240V AC - Diesel 150 A
Service Rated Transfer Switch No
Engine Speed 1,800 RPM
Transfer Switch Included No
Fuel Type Diesel
Noise Level 70 dBA
12V DC Battery Charger Yes
Running Wattage - Diesel 50 kW
Is this a Hazardous Material Product? N
Safety Features Charger Fault, Low Oil Warning, Low Coolant Level Shutdown, Exerciser Set Error Warning, High Temperature Shutdown, Incorrect Wiring Protection, Common External Fault Capability, Safety Fused, Automatic Voltage Regulator (AVR), Run Time Hour Meter, Low Battery Protection, Battery Problem Protection
Fuel NPT Pipe Connection Size 2 in
Run Time @ 1/2 Load - Diesel 28.2 hr
Starter Type 12V
Wi-Fi Equipped Yes
Carbon Monoxide Protection No Carbon Monoxide Detection
Includes Two Line LCD Multilingual Digital Evolution Controller, Isochronous Electric Governor, Smart Battery Charger
Main Circuit Breaker 175 A
Product Powered by Fossil Fuel N
Power Factor 0.8
Safety Data Sheet (SDS) Applicable? N
Should Sales be Restricted by Region? N
Enclosure Material Aluminum
Standards CSA Certified, UL 2200, UL 142, ULC S601, EGSA, CA/MA, EPA, NEMA
Engine Brand Generac
Hazmat_Message Compliance_Hazmat_ExcEngines
Exercise Cycle Duration 90 sec
Apparent Power Rating 85 kVA
Engine Cooling Liquid
Overall Length 95 in
RoHS - Restricted Use of Hazardous Substances Directive (RoHS) N
Fuel Tank Capacity 57 gal
Engine Type OHV
Includes Battery No
Manufacturer Warranty 5 yr
Ozone Depleting Substance N
Phase Three
Rated Frequency 60 Hz
EnvironmentallyPreferable_Indicator N
Overall Height 57 in
California Prop 65 Reproductive Harm N
Battery CCA Rating 700 CCA
Freight Class Code 250
Exercise Cycle Interval 7 day
Sub-brand Diesel Protector Series
Rated Voltage 120/240V AC
Amp Rating - Diesel 150 A
Storage Protection Code A
Overall Width 35 in
Mfr. Model # RD05033JDAE
Description

Stdby Gen, 3PhaseDiesel, 50 kW/150 A, CARB

Catalog Page 947